Mr. Study
Craftsman Electrician study guide

Problem 14 control — AND/OR inputs and timed stopping

Last updated: 2026-10-05 · 3 min read

Created and edited by Mr. Study · About and editorial approach · Report a correction

Try the contact-logic exercise on this page, no sign-in ↓

Problem 14 compares two different start conditions using the same two sensors. PB1 needs both LS inputs; PB2 needs at least one. This lesson uses the Q-Net 2025-08-04 edition and the site's problem-14 example. The earlier automatic forward/reverse explanation was incorrect for this problem.

Read the power circuit and self-hold lesson first. M1 and M2 are separate loads. Changing an LS state is not an automatic command to start the other motor.

Original Mr. Study logic summary: PB1 needs both inputs; PB2 needs either input. Each branch stops through its own timer.
Original Mr. Study logic summary: PB1 needs both inputs; PB2 needs either input. Each branch stops through its own timer.

Read the sensors first

LS1 drives the X1 relay state and LS2 drives X2. In the first operating path, their NO contacts are in series; in the second, they are in parallel. The exam notice treats LS devices as external switches connected through a terminal block. Distinguish that supplied-material scope from the clickable LS symbols in the simulator.

LS1LS2PB1 can start MC1PB2 can start MC2
ReleasedReleasedNoNo
DetectedReleasedNoYes
ReleasedDetectedNoYes
DetectedDetectedYesYes

This assumes the protection/stop path and other starting conditions are satisfied. The last row does not establish mutual exclusion between the motors. Do not add a reversing interlock that is absent from this circuit.

Trace one branch completely

  1. From the fused supply, find the healthy EOCR contact and PB0 stop contact first. The control supply is L1/L3, not L1/neutral.
  2. PB1 can energize MC1 and T1 through the series X1/X2 condition and T1's timed NC path.
  3. T1's instantaneous contact supplies the holding path around PB1. Releasing START does not remove the need for the sensor and stop conditions.
  4. When T1 expires, the timed NC path opens and MC1/T1 drop out. Releasing either LS also breaks the series condition.
  5. Read the PB2 branch with X1/X2 in parallel instead. T2 expiry or release of both LS inputs stops MC2/T2.

MC auxiliary contacts also control RL/GL and standby lamp WL. Not every NC contact is a reversing interlock: follow what load is connected after it.

Test the example

The saved site example sets T1 and T2 to five seconds each. Do not interpret the official t1/t2 notation as a universal five-second setting.

ActionExpected result
Breaker ON, before startingStandby indicator WL
Both LS detected; press/release PB1MC1/T1 and M1/RL operate
T1 expires or either LS releasesMC1 stops
One LS detected; press/release PB2MC2/T2 and M2/GL operate
T2 expires or both LS releaseMC2 stops
Press PB0 while runningOperating circuit stops
Trip EOCR while runningOperation stops; YL alarm
Reset EOCR after addressing the causeReturn to initial state; verify a new start command

Work backwards from a fault

SymptomPossible mistakeQuestion to check
PB1 works with only one LSX1/X2 wired in parallelAre both NO contacts in the same series path?
PB2 also requires both LSX1/X2 wired in seriesCan one parallel branch complete the condition?
Stops as soon as START is releasedHolding path omittedDoes the timer's instantaneous contact bypass START?
Keeps running after timer expiryTimed NC bypassed or wrong contact usedMust coil supply pass through the timed NC?

Exercise and answer

Question: With only LS1 detected, why do PB1 and PB2 behave differently? Answer: PB1 has an open contact in its series condition. PB2 has one closed parallel branch, which is sufficient. Compare input logic, not motor direction.

Open practical projects →. After signing in, use a problem-14 project and change the sensors in the order above. The link does not preload a completed solution. These are virtual testing steps, not instructions to energize equipment during an exam.

References and limits

Q-Net public problems, 2025-08-04 edition, problem 14 pages 11-7 to 11-9: circuit, operation and component diagrams. The original logic illustration here is a learning summary, not a replacement circuit drawing. The simulator calculates virtual contacts; it does not model actual overload current or mechanical motion.

Test the contact logic here

Open the interactive exercise below →. No sign-in is needed; the instructions and results explain exactly which part of the circuit is being modeled.

Try without signing in: AND/OR conditions with two sensors

Detect LS1 alone and compare both paths. Then detect LS2 too. This exercise shows start permissions only; it does not model running motors, timers or stopping.

A contact-logic learning model, not a hardware wiring or ratings check. Active buttons are highlighted.

PB1 → MC1 (AND)
Start blocked
PB2 → MC2 (OR)
Start blocked

Read the holding-path explanation · Open the homepage wiring simulator

Related guides